Co-Packaged Optics Goes Live: What It Means for Your Fiber Plant

CPO switches are now in large-scale use. Here is what changes for fiber counts, singlemode, lasers and serviceability, and what stays the same.

By Todd Taskerud, AWS CCP, RCDD/NTS/OSP/WD, LEED GA
5 min read

Technician inspecting a dense bank of singlemode fiber connections on a liquid-cooled network switch in an AI data center

Co-packaged optics (CPO) has moved from keynote announcements into a deployment at scale. On November 16, during SC26 in Chicago, NVIDIA reported that cloud provider Lambda is using NVIDIA Photonics CPO switches to connect NVIDIA GB300 NVL72 racks with more than 10,000 GPUs. For the people who design, buy, and install fiber, the practical question is what changes at the switch, and what stays the same in the cabling plant.

From Announcement to Deployment

NVIDIA unveiled its Spectrum-X Photonics (Ethernet) and Quantum-X Photonics (InfiniBand) switches at GTC on March 18, 2025. The announcement described Spectrum-X Photonics configurations of 128 ports of 800Gb/s or 512 ports of 200Gb/s (100Tb/s total), and 512 ports of 800Gb/s or 2,048 ports of 200Gb/s (400Tb/s total), plus Quantum-X Photonics switches with 144 ports of 800Gb/s InfiniBand in a liquid-cooled design. NVIDIA's named ecosystem included TSMC, Corning Incorporated, SENKO, Coherent, Lumentum, Fabrinet, and Foxconn, among others.

Broadcom followed on October 8, 2025, announcing Tomahawk 6 – Davisson (TH6-Davisson), which it describes as its third-generation CPO Ethernet switch and the industry's first to deliver 102.4 terabits per second of optically enabled switching capacity. Broadcom's SC26 preview post, dated November 10, names TH6-Davisson among the technologies behind the open Ethernet fabric it planned to show at its booth.

The Lambda deployment, described in NVIDIA's November 16 blog post, uses NVIDIA Photonics switches with 144 ports each running at 800Gb/s, with liquid cooling carrying heat away from the switch chip and optical engines. According to NVIDIA, Lambda's tests showed network latency dropping by about 4% at rack scale and by up to about 10% at pod scale, while the network maintained the same throughput as conventional pluggable optics.

What CPO Changes

The transceiver moves onto the switch package

In a conventional switch, every front-panel port takes a pluggable transceiver. With CPO, the optical engines sit on the same package as the switch chip. NVIDIA says co-packaging shortens the electrical path "from inches to millimeters" and removes the need for retimer chips. Broadcom says co-packaging "eliminates the need to source and manage high-speed pluggable transceivers in deployment." On the switch side of a CPO link, separately purchased transceivers drop off the bill of materials.

Lasers become a separate, field-replaceable part

This is the biggest serviceability change. According to NVIDIA, each switch in Lambda's deployment has 18 removable external light sources that supply light to the optical engines. In NVIDIA's words, "Technicians can replace the light-source modules in the field, unlike traditional pluggable optics, which require replacing the entire module if a laser fails." NVIDIA also says the design uses 4x fewer lasers. Broadcom lists field-replaceable ELSFP laser modules among the TH6-Davisson product highlights. Spares planning shifts from transceivers to laser modules.

Fiber counts at the switch are high, and singlemode

Broadcom's BCM78919 product page is specific: the integrated optical engines connect to the front panel using 512 duplex single-mode optical fibers, and each duplex fiber supports 200GbE, 100GbE, or 50GbE "using a single wavelength at 1310 nm." That is 1,024 fibers leaving a single switch, with port configurations such as 64 × 1.6TbE or 128 × 800GbE. Inside the chassis, the fiber between faceplate and chip is part of the switch system; Corning, quoted in Broadcom's release, describes "complete faceplate-to-chip optical assemblies for TH6-Davisson systems." Your cabling scope starts at the faceplate.

What CPO Does Not Change

  • Pluggables still have a place. NVIDIA's own launch release said its photonics switches would drive growth "alongside pluggable optical transceiver technologies." Broadcom says TH6-Davisson interconnects with DR-based transceivers as well as LPO and CPO optical interconnects running at 200 Gbps per channel, and claims IEEE 802.3 compliance, interoperable with existing 400G and 800G standards. The far end of a CPO link can still be a pluggable.
  • The link is still a singlemode fiber link. Loss budgets, polarity, and certification testing all still apply. Our guides to designing 400G and 800G fabrics for NVIDIA AI clusters and preparing your fiber plant for 802.3dj cover the planning basics that carry straight over.
  • Connector choice still has to be confirmed. None of the NVIDIA or Broadcom material we reviewed names the front-panel connector type. Whether a system uses MPO-style or very small form factor connectors, confirm it with the system vendor before ordering trunks and cords. See our overview of VSFF connectors such as SN and MDC.
  • Clean endfaces still matter. A contaminated connector degrades a CPO link just as it does any other. The difference is that there is no pluggable transceiver on the switch side to swap out, so getting the fiber interface right the first time matters more. See fiber inspection and cleaning.

What to Do Now

If CPO switches are on a roadmap you support, a few steps now will save rework later:

  • Get the faceplate details early. Ask the system vendor for the connector type, fiber count per port, polarity method, and fiber type before designing trunks and patch fields.
  • Size pathways for density. At 1,024 fibers per 102.4 Tb/s switch (per Broadcom's figures), tray fill, patch-panel capacity, and bend-radius management need to be planned around the switch, not added later.
  • Plan singlemode. Broadcom specifies single-mode fiber at the TH6-Davisson faceplate, so plan singlemode cabling between switch tiers and confirm the exact fiber type with the vendor.
  • Add laser modules to spares and runbooks. Confirm the replacement procedure, the stocking level, and who on site is trained to perform it.
  • Coordinate with liquid cooling. NVIDIA's Quantum-X Photonics switches and Lambda's deployment are liquid-cooled. Plan fiber and coolant routing together, with clear separation and service access.
  • Equip every crew to inspect. Inspection scopes and cleaning tools belong on every job that touches a CPO faceplate.
  • Keep pluggable plans in place. Other tiers of the network and far-end devices may still use transceivers, so procurement for them continues.

Closing Thoughts

CPO moves the transceiver into the switch, makes the laser a field-replaceable module, and, in Broadcom's 102.4 Tb/s design, brings more than a thousand singlemode fibers to a single switch faceplate. It does not change the fundamentals: clean connectors, sound loss budgets, careful polarity, and well-planned pathways. Heather Technologies helps government, research, and commercial customers source the fiber, connectivity, optics-ready infrastructure, and test equipment behind high-performance networks. If CPO is on your horizon, talk to our team about getting your fiber plant ready.